如何计算Motor Sizing

learn.whatIsHeading

Motor sizing matches horsepower to load requirements. Over-sizing wastes energy; under-sizing risks overheating and failure.

公式

Calculate: P = (T × RPM) / 5252 for mechanical power
P
(T × RPM) / 5252 for mechanical power — (T × RPM) / 5252 for mechanical power
T
T value — Variable used in the calculation
RPM
RPM value — Variable used in the calculation

分步指南

  1. 1Calculate: P = (T × RPM) / 5252 for mechanical power
  2. 2Apply service factor 1.15-1.25 for continuous duty
  3. 3Select standard motor size meeting service factor requirement

例题解析

输入
Pump load 7.5 kW continuous, service factor 1.25
结果
Motor = 7.5 × 1.25 = 9.4 kW, select 10 kW standard motor
Next size up

常见错误注意事项

  • Using continuous rating for intermittent duty
  • Neglecting starting current requirements

常见问题

What is service factor?

Allowable overload margin (typically 1.15-1.25); accounts for load variations and starting surges.

Why not over-size motors?

Larger motors are less efficient at partial load; match size to duty point.