Skip to main content
Skip to main content
DigiCalcs

learn.howToCalculate

learn.whatIsHeading

Heat exchanger effectiveness and sizing depend on flow rates, temperatures, and heat transfer area. Design ensures adequate thermal transfer.

Formel

Calculate: Q = U×A×ΔT_lm (log mean temperature difference)
Q
U×A×ΔT_lm (log mean temperature difference) — U×A×ΔT_lm (log mean temperature difference)
U
U value — Variable used in the calculation
A
A value — Variable used in the calculation

Trin-for-trin guide

  1. 1Calculate: Q = U×A×ΔT_lm (log mean temperature difference)
  2. 2Account for flow arrangement (counterflow, cross-flow, parallel)
  3. 3Size area for required heat transfer

Løste eksempler

Input
Q = 50 kW, U = 2000 W/m²·K, ΔT_lm = 10 K
Resultat
A ≈ 2.5 m² required
Determines exchanger size

Almindelige fejl at undgå

  • Using arithmetic mean instead of log mean temperature difference
  • Neglecting fouling resistance

Ofte stillede spørgsmål

Why is counterflow more efficient?

Counterflow maximizes temperature driving force throughout; parallel-flow has smaller LMTD.

What determines overall U coefficient?

U depends on fouling, scale, fluid properties. Typical 500-5000 W/m²·K depending on fluids.

Klar til at beregne? Prøv den gratis Heat Exchanger-beregner

Prøv det selv →

Indstillinger

PrivatlivVilkårOm© 2026 DigiCalcs