Skip to main content
DigiCalcs

learn.howToCalculate

learn.whatIsHeading

Voltage Drop Calculator helps contractors and tradespeople accurately size, spec, and estimate materials and systems.

الصيغة

VD = (2 × K × I × L) / CM where K=12.9(Cu), I=amps, L=feet, CM=circular mils

دليل خطوة بخطوة

  1. 1Enter circuit amps, one-way distance, and wire gauge circular mils
  2. 2Apply the formula using your project measurements
  3. 3Add required safety factors or waste allowances per code

أمثلة محلولة

الإدخال
15A, 100 ft, 12 AWG (6530 CM)
النتيجة
VD = (2×12.9×15×100)/6530 = 5.94V = 4.95% (max 3% recommended)

أخطاء شائعة يجب تجنبها

  • Not applying code-required safety factors or derating
  • Forgetting to account for waste and cut losses in material estimates

هل أنت مستعد للحساب؟ جرب الآلة الحاسبة Voltage Drop المجانية